2 Parameters
2.2 List of parameters
SINAMICS G130/G150
678
List Manual (LH2), 07/2016, A5E03263479A
Dependency:
Refer to: r4105, r4112, r4113, r4114
Notice:
When forming groups, it must be ensured that in one particular group, only temperature channels with the following
sensor types are included:
- "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6), real temperature actual value
or alternatively
- "PTC thermistor", "bimetallic NC contact" (p4100[0...11] = 1, 4), fictitious temperature actual value (-50 °C, 250 °C)
If these sensor types are combined within one group, then the calculated values for maximum, minimum and average
value will be falsified.
Note:
Active and inactive temperature channels can be included in one group. However, when calculating the values
(r4112, r4113, r4114) only the active temperature channels with valid actual value are taken into account
(r4105[0...11] not equal to -300 °C).
Description:
Display and connector output for the maximum value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation:
The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index:
[0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency:
Refer to: r4105, p4111, r4113, r4114
Description:
Display and connector output for the minimum value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation:
The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index:
[0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency:
Refer to: r4105, p4111, r4112, r4114
07
Temperature channel 7
Yes
No
-
08
Temperature channel 8
Yes
No
-
09
Temperature channel 9
Yes
No
-
10
Temperature channel 10
Yes
No
-
11
Temperature channel 11
Yes
No
-
r4112[0...2]
CO: TM150 group temperature actual value maximum value / TM150 grp temp max
TM150
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9625
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2006
Expert list:
1
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
r4113[0...2]
CO: TM150 group temperature actual value minimum value / TM150 grp temp min
TM150
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9625
P-Group:
Terminals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
p2006
Expert list:
1
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......