SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
125
2 Parameters
2.2 List of parameters
Description:
Displays the status word of the cooling unit.
Dependency:
Refer to: p0266
Description:
Sets the absolute value by which the threshold to initiate the undervoltage fault (F30003) is reduced.
Dependency:
Refer to: p0210, r0296
Refer to: F30003
Notice:
When using a Control Supply Module (CSM) for 24 V supply from the DC link, the minimum continuous DC link
voltage may not lie below 430 V. DC link voltages in the range 300 ... 430 V are permissible up to a duration of 1 min.
For chassis power units, this parameter has no significance.
Note:
The resulting shutdown threshold can be read in r0296 and is dependent on the selected rated voltage (p0210) and
the power unit being used.
Description:
Sets the voltage threshold to initiate alarm A06810.
The value represents an offset so that the alarm threshold is obtained from the total of r0296 and p0279.
Dependency:
Refer to: p0210, r0296
Refer to: A06810
Note:
The absolute value of the undervoltage threshold r0296 depends on the selected unit supply voltage (p0210).
r0267.0...7
BO: Cooling unit status word / RKA ZSW
VECTOR_G
(Cool_unit), B_INF
(Cool_unit)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
RKA switched on
Yes
No
-
01
RKA ready for switching on
Yes
No
-
02
RKA no alarm present
Yes
No
-
03
RKA no fault present
Yes
No
-
04
RKA no leaked fluid
Yes
No
-
05
RKA liquid flow OK
Yes
No
-
06
RKA conductivity no fault
Yes
No
9974
07
RKA conductivity no alarm
Yes
No
9974
p0278
DC link voltage undervoltage threshold reduction / Vdc U_under red
VECTOR_G
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
-80 [V]
0 [V]
0 [V]
p0279
DC link voltage offset alarm threshold / Vdc offs A thresh
B_INF
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
8760, 8864,
8964
P-Group:
Converter
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [V]
500 [V]
0 [V]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......