SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
609
2 Parameters
2.2 List of parameters
Description:
Sets the scaling factor for the power pre-control.
Dependency:
Refer to: p3520
Note:
The scaling factor acts on the sum of the associated indices of p3519 and p3520. As one BICO input is scaled
(p3519) and the other is not scaled (p3520), for each index, only one of the two inputs should be assigned.
Description:
Display and connector output for the smoothed power precontrols.
Index:
[0] = Power precontrol 1
[1] = Power precontrol 2
[2] = Power precontrol 3
[3] = Power precontrol 4
[4] = Power precontrol sum linearized
Dependency:
Refer to: p3520, p3521, p3523
Note:
These displays are used to set the correct scaling for the pre-control.
Description:
Sets the filter time for power pre-control.
Dependency:
Refer to: p3520
Description:
Display of the DC link voltage controller output (Vdc controller).
Index:
[0] = I output
[1] = PI output
p3521[0...3]
DC link pre-control power scaling / Vdc prectrl P scal
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7960
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-100000.00000 [%]
100000.00000 [%]
100.00000 [%]
r3522[0...4]
CO: DC link voltage control precontrol display / Vdc_ctr prectr dis
VECTOR_G
(Tech_ctrl)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7960
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [kW]
- [kW]
- [kW]
p3523[0...3]
DC link pre-control power smoothing / Vdc pre-ctrl P sm
VECTOR_G
(Tech_ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
1000 [ms]
0 [ms]
r3554[0...1]
Vdc controller output / INF Vdc_ctrl outp
VECTOR_G
(Tech_ctrl)
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
7960
P-Group:
Closed-loop control
Unit group:
6_2
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2002
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......