2 Parameters
2.2 List of parameters
SINAMICS G130/G150
880
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the IP address for the onboard PROFINET interface on the Control Unit.
The actual IP address is displayed in r8931.
Dependency:
Refer to: p8925, r8931
Note:
The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
Description:
Sets the default gateway for the onboard PROFINET interface on the Control Unit.
The actual standard gateway is displayed in r8932.
Dependency:
Refer to: p8925, r8932
Note:
The setting p8922[0...3] = 0 or p8922 = p8921 (own IP address) means that a standard gateway has not been set.
The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
Description:
Sets the subnet mask for the onboard PROFINET interface on the Control Unit.
The actual subnet mask is displayed in r8933.
Dependency:
Refer to: p8925, r8933
Note:
The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
Description:
Sets the DHCP mode for the onboard PROFINET interface on the Control Unit.
The actual DHCP mode is displayed in r8934.
Value:
0:
DHCP off
2:
DHCP on, identification using MAC address
3:
DHCP on, identification via name of station
p8921[0...3]
PN IP address / PN IP addr
CU_G130_PN,
CU_G150_PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 255
0
p8922[0...3]
PN Def Gateway / PN Def Gateway
CU_G130_PN,
CU_G150_PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 255
0
p8923[0...3]
PN Subnet Mask / PN Subnet Mask
CU_G130_PN,
CU_G150_PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 255
0
p8924
PN DHCP Mode / PN DHCP mode
CU_G130_PN,
CU_G150_PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......