SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
789
2 Parameters
2.2 List of parameters
Description:
Sets the mode for the sub-boot.
Value:
0:
Sub-boot manual
1:
Sub-boot automatic
Note:
For p7857 = 0 (manual sub-boot) the following applies:
The parameter should be set to 1 to start the sub-boot.
Description:
Sets the global and unique component number in a drive system with several Control Units.
Each index of the parameter corresponds to a possible local component number on the corresponding Control Unit.
The indices are allocated to the global component numbers as follows:
p7859[0]: Not used
p7859[1]: Sets the global component number for the local component number 1
p7859[2]: Sets the global component number for the local component number 2
...
p7859[199]: Sets the global component number for the local component number 199
Notice:
This parameter is preferably set via suitable commissioning software (e.g. UpdateAgent, STARTER, SCOUT).
Changing the parameter via the AOP (Advanced Operator Panel) or BOP (Basic Operator Panel) can destroy a valid
unique setting.
Note:
The parameter is not influenced by setting the factory setting.
Description:
Displays status and configuration changes of all of the drive objects in the complete unit.
When changing the status or the configuration of the Control Unit or a drive object, the value of this parameter is
incremented.
Dependency:
Refer to: r7868, r7869, r7870
p7857
Sub-boot mode / Sub-boot mode
VECTOR_G, B_INF,
TM31, TM120, TM150,
TB30, TM54F_MA,
TM54F_SL, ENC, HUB
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
1
p7859[0...199]
Component number global / Comp_no global
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
-32786 32767
0
r7867
Status/configuration changes global / Changes global
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
-
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......