2 Parameters
2.2 List of parameters
SINAMICS G130/G150
446
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the speed threshold value to detect a stalled motor.
If the adaptation controller output exceeds the parameterized speed difference, then in status word r1408.11 is set =
1.
Dependency:
If a stalled drive is detected (r1408.11 = 1), fault F07902 is output after the delay time set in p2178.
Refer to: p2178
Note:
Speed monitoring is only effective in operation with a speed encoder (refer to p1300).
Stalling is also identified if steps/jumps occur in the speed signal, which exceed the value in p0492.
Description:
Sets the fault threshold in order to detect a motor that has stalled.
If the error signal (r1746) exceeds the parameterized error threshold, then status signal r1408.12 is set to 1.
Dependency:
If a stalled drive is detected (r1408.12 = 1), fault F07902 is output after the delay time set in p2178.
Refer to: p2178
Note:
Monitoring is only effective in the low-speed range (below p1755 * (100% - p1756)).
Description:
Signal to initiate stall detection
Note:
The signal is not calculated while magnetizing and only in the low speed range (below p1755 * (100 % - p1756)).
Description:
Sets the lower speed for the transition "n_set -> n_act" in encoderless operation.
This value is entered as a percentage referred to p1749.
Dependency:
Refer to: p1749, p1752
p1744[0...n]
Motor model speed threshold stall detection / MotMod n_thr stall
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
SESM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
100.00 [rpm]
p1745[0...n]
Motor model error threshold stall detection / MotMod ThreshStall
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
1000.0 [%]
5.0 [%]
r1746
Motor model error signal stall detection / MotMod sig stall
VECTOR_G (n/M)
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [%]
- [%]
- [%]
p1748[0...n]
Motor model lower changeover speed n_set -> n_act / MotMod low n_chng
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
ASM, PMSM, REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
90.0 [%]
50.0 [%]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......