2 Parameters
2.2 List of parameters
SINAMICS G130/G150
704
List Manual (LH2), 07/2016, A5E03263479A
[2] = Trace 0 PINx with DO Id and chart Id
[3] = Trace 0 PINx with block Id and PIN Id
[4] = Trace 1 PINy with DO Id and chart Id
[5] = Trace 1 PINy with block Id and PIN Id
Dependency:
Only effective when p4710 does not equal 1.
Note:
It only makes sense to trace the PINs using the commissioning software.
For index 2(4) and 3(5) equal to zero, index 0(1) can only be written and vice versa.
For index 0 ... 1:
Here, the trigger signal for trace 0 or 1 is entered as parameter in the BICO format.
For trace with a physical address (p4789), the data type of the trigger signal is set here.
For index 2 ...3:
The triggering PIN for trace 0 is entered here.
Index 2 bit 31 ... 16: Number of the Drive Object (DO), bit 15 ... 0: Number of the chart
Index 3 bit 31 ... 16: Number of the block, bit 15 ... 0: Number of the PIN
For index 4 ... 5:
The triggering PIN for trace 1 is entered here.
Index 4 bit 31 ... 16: Number of the Drive Object (DO), bit 15 ... 0: Number of the chart
Index 5 bit 31 ... 16: Number of the block, bit 15 ... 0: Number of the PIN
Description:
Sets the trigger threshold for the trace.
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Only effective when p4710 = 2, 3.
Description:
Sets the first trigger threshold for trigger via tolerance band.
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Only effective when p4710 = 4, 5.
Description:
Sets the second trigger threshold for trigger via tolerance band
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Only effective when p4710 = 4, 5.
p4712[0...1]
Trace trigger threshold / Trace trig_thresh
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
-340.28235E36 340.28235E36
0.00
p4713[0...1]
Trace tolerance band trigger threshold 1 / Trace trig thr 1
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
-340.28235E36 340.28235E36
0.00
p4714[0...1]
Trace tolerance band trigger threshold 2 / Trace trig thr 2
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
-340.28235E36 340.28235E36
0.00
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...