2 Parameters
2.2 List of parameters
SINAMICS G130/G150
646
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the limit for the total output voltage of terminals X541.1, X541.2, X541.3 and X541.4 (DI/DO 8 ... 11) of Terminal
Module 31 (TM31).
Value:
0:
0.1 A total current limit DI/DO 8 ... 11
1:
1.0 A total current limit DI/DO 8 ... 11
Dependency:
Refer to: p4028
Warning:
Since the sum of the output currents at terminals X541.1, X541.2, X541.3 and X541.4 is limited, an overcurrent or
short circuit at one output terminal can cause a dip in the signal at the other terminals.
Description:
Displays the status of the digital outputs of Terminal Module 31 (TM31).
Note:
Inversion using p4048 has been taken into account.
The setting of the DI/DO as either input or output is of no significance (p4028).
DO: Digital Output
DI/DO: Bidirectional Digital Input/Output
Description:
Displays the status of the digital outputs of the Terminal Board 30 (TB30).
Note:
Inversion using p4048 has been taken into account.
DO: Digital Output
p4046
TM31 digital outputs limit current / TM31 DO limit curr
TM31
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
9560
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
r4047
TM31 digital outputs status / TM31 DO status
TM31
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
9556, 9560,
9562
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (X542.1 - 3)
High
Low
-
01
DO 1 (X542.4 - 6)
High
Low
-
08
DI/DO 8 (X541.2)
High
Low
-
09
DI/DO 9 (X541.3)
High
Low
-
10
DI/DO 10 (X541.4)
High
Low
-
11
DI/DO 11 (X541.5)
High
Low
-
r4047
TB30 digital outputs status / TB30 DO status
TB30
Can be changed:
-
Calculated:
-
Access level:
1
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
9102
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (X481.5)
High
Low
-
01
DO 1 (X481.6)
High
Low
-
02
DO 2 (X481.7)
High
Low
-
03
DO 3 (X481.8)
High
Low
-
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......