2 Parameters
2.2 List of parameters
SINAMICS G130/G150
396
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the integration time of the speed controller before the adaptation speed range (0 ... p1464).
This value corresponds to the basic setting of the integral time of the speed controller without adaptation (p1461 =
100 %).
Dependency:
Refer to: p1463, p1464, p1465
Note:
The integral component is stopped if the complete controller output or the sum of controller output and torque pre-
control reach the torque limit.
Description:
Sets the integral time of the speed controller after the adaptation speed range (> p1465).
The entry is made referred to the integral time for the lower adaptation speed range of the speed controller (%
referred to p1462).
Dependency:
Refer to: p1462, p1464, p1465
Note:
If the upper transition point p1465 of the speed controller adaptation is set to lower values than the lower transition
point p1464, then the controller integral time below p1465 is adapted with p1463. This means that an adaptation can
be implemented for low speeds without having to change the controller parameters.
Description:
Sets the lower adaptation speed of the speed controller.
No adaptation is effective below this speed.
Dependency:
The parameter is set by the speed controller optimization. Adaptation to the application should then be subsequently
made.
Refer to: p1460, p1461, p1462, p1463, p1465
Note:
If the upper transition point p1465 of the speed controller adaptation is set to lower values than the lower transition
point p1464, then the controller below p1465 is adapted with p1461 or p1463. This means that an adaptation can be
implemented for low speeds without having to change the controller parameters.
p1462[0...n]
Speed controller integral time adaptation speed lower / n_ctrl Tn n lower
VECTOR_G
(J_estimator, n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
5040, 5042,
6020, 6040
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
100000.00 [ms]
20.00 [ms]
p1463[0...n]
Speed controller Tn adaptation speed upper scaling / n_ctr Tn n up scal
VECTOR_G
(J_estimator, n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
200000.0 [%]
100.0 [%]
p1464[0...n]
Speed controller adaptation speed lower / n_ctrl n lower
VECTOR_G (n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6050
P-Group:
Closed-loop control
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
0.00 [rpm]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......