SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
231
2 Parameters
2.2 List of parameters
Caution:
If, for a selected temperature sensor (p0600 > 0), the motor temperature sensor is not connected but another sensor,
then the temperature adaptation of the motor resistances must be switched out. Otherwise, in controlled-loop
operation, torque errors will occur that will mean that the drive will not be able to be stopped.
Notice:
The parameter is calculated in the drive using p0340 and is inhibited for p0340 > 0.
For operation with a braking resistor (p1300 = 15), p0600 = 11 is automatically set when commissioning.
Note:
For p0600 = 0:
With induction motors, the motor temperature is calculated using the motor temperature model (see also p0612.1).
For p0600 = 1, 2, 3:
Bimetallic switch (p0601 = 4) and PT100 temperature sensor (p0601 = 5) are not supported.
For p0600 = 10:
The BICO interconnection should be executed via connector input p0603.
For p0600 = 11:
For SINAMICS S120 AC Drive (AC/AC) and using the Control Unit Adapter CUA31, the temperature sensor is
connected at the adapter (X210).
For p0600 = 20, 21:
The BICO interconnection should be executed via connector input p0608 or p0609.
Associated parameters: p0601, p4600 ... p4603, p4610 ... p4613
Description:
Sets the sensor type for the motor temperature monitoring.
Value:
0:
No sensor
1:
PTC alarm & timer
2:
KTY84
3:
KTY84 and PTC (only for motors with DRIVE-CLiQ):
4:
Bimetallic NC contact alarm & timer (only for temp_eval via MM)
5:
PT100
6:
PT1000
7:
PT1000 and PTC (only for motors with DRIVE-CLiQ):
10:
Evaluation via several temperature channels SME12x
11:
Evaluation via several temperature channels BICO
Dependency:
A thermal motor model is calculated corresponding to p0612.
Refer to: r0458, p0600, p0612
Note:
The temperature sensor for the temperature evaluation is set in p0600.
For p0600 = 10 (temperature sensor via a BICO interconnection), the setting in p0601 has no significance.
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
For p0601 = 1:
Tripping resistance = 1650 Ohm.
After the tripping resistance has been exceeded, an appropriate alarm is output and after the delay time set in p0606
has expired, an appropriate fault is output.
For p0601 = 3, 7:
For motors with DRIVE-CLiQ and two temperature sensors, the value is automatically set.
For p0601 = 4:
Tripping resistance = 100 Ohm.
After tripping, an appropriate alarm is output and after the delay time set in p0606 has expired, an appropriate fault is
output.
For p0601 = 5:
It is only possible to evaluate a PT100 for p0600 = 11 and r0192.15 = 1.
p0601[0...n]
Motor temperature sensor type / Mot_temp_sens type
VECTOR_G
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
MDS, p0130
Func. diagram:
8016
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 11
2
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......