2 Parameters
2.2 List of parameters
SINAMICS G130/G150
560
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the scaling factor for torque utilization (r0033).
Description:
Display and BICO output for the first status word of the monitoring functions.
Note:
For bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
For bit 03:
The hysteresis is set in p2150.
For bit 06:
The hysteresis is set in p2162.
For bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
For bit 13:
Only for internal Siemens use.
Description:
Display and BICO output for the second status word of the monitoring functions.
p2196[0...n]
Torque utilization scaling / M_util scal
VECTOR_G
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
1
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Motor
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [%]
1000.00 [%]
100.00 [%]
r2197.1...13
CO/BO: Status word monitoring 1 / ZSW monitor 1
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
2534
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
|n_act| <= speed threshold value 2 p2155
Yes
No
8010
02
|n_act| > speed threshold value 2 p2155
Yes
No
8010
03
n_act >= 0
Yes
No
8011
06
|n_act| > n_max
Yes
No
8010
07
Speed setp - act val deviation in tolerance
t_off
Yes
No
8011
13
|n_act| > n_max (F07901)
Yes
No
-
r2198.4...12
CO/BO: Status word monitoring 2 / ZSW monitor 2
VECTOR_G
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
2536
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
04
|n_set| < p2161
Yes
No
8011
05
n_set > 0
Yes
No
8011
06
Motor blocked
Yes
No
8012
07
Motor stalled
Yes
No
8012
10
|M_set| < torque threshold value 1
Yes
No
8012
11
Load in the alarm range
Yes
No
8013
12
Load in the fault range
Yes
No
8013
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......