2 Parameters
2.2 List of parameters
SINAMICS G130/G150
600
List Manual (LH2), 07/2016, A5E03263479A
Description:
Sets the delay time for the zero current signal for the zero current monitoring.
Dependency:
Refer to: p3207, p3208
Note:
The monitoring function is only carried out for separately excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold in p2161 (r2199.0 = 1).
Description:
Sets the time constant for the PT1 element to smooth the torque actual value.
The smoothed torque actual value is compared with the threshold values and is only used for messages and signals.
Description:
Sets the monitoring time for phase failure detection of the motor.
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
Monitoring is only effective for blocksize and booksize power units.
For p3235 = 0 the function is deactivated.
For VECTOR, the following applies:
The monitoring is automatically deactivated during a flying restart for a motor that is still rotating.
Description:
Sets the speed threshold value for the signal "speed deviation model/external in tolerance" (BO: r2199.7).
Dependency:
Refer to: r1443, r2169, r2199, p3237
p3209[0...n]
Zero current signal delay time / I_0_sig t_del
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
-
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
ASM, PMSM, REL,
RESM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [s]
10.00 [s]
0.02 [s]
p3233[0...n]
Torque actual value filter time constant / M_act_filt T
VECTOR_G (Ext msg)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
8013
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
1000000 [ms]
0 [ms]
p3235
Phase failure signal motor monitoring time / Ph_fail t_monit
VECTOR_G
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
2000 [ms]
320 [ms]
p3236[0...n]
Speed threshold value 7 / n_thresh val 7
VECTOR_G
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
8012
P-Group:
Messages
Unit group:
3_1
Unit selection:
p0505
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [rpm]
3000.00 [rpm]
100.00 [rpm]
Содержание SINAMICS G130
Страница 1: ...s SINAMICS SINAMICS G130 G150 List Manual 07 2016 Edition ...
Страница 2: ......
Страница 8: ...Preface SINAMICS G130 G150 8 List Manual LH2 07 2016 A5E03263479A ...
Страница 1940: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G130 G150 1940 List Manual LH2 07 2016 A5E03263479A ...
Страница 1960: ...A Appendix A 3 References SINAMICS G130 G150 1960 List Manual LH2 07 2016 A5E03263479A ...
Страница 1974: ...Index SINAMICS G130 G150 1974 List Manual LH2 07 2016 A5E03263479A ...
Страница 1975: ......