![Siemens SINAMICS S Series List Manual Download Page 98](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_1265427098.webp)
Parameters
List of parameters
1-98
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Detects the power unit assigned to this drive and data set.
Note:
While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate power unit.
For parallel circuit configurations, the parameter index is assigned to a power unit.
Description:
Setting to activate/de-activate a power unit component.
Values:
0:
De-activate component
1:
Activate component
2:
Component, de-activate and not present
Recommend.:
After inserting a component, before activating, first wait for Alarm A01317.
Dependency:
Refer to: r0126
Refer to: A01317
Caution:
It is not permissible to de-activate drive objects with safety functions enabled.
Note:
The activation of a component can be rejected if the component was inserted for the first time.
In this case, it is only possible to activate the component when the pulses for all of the drive objects are inhibited.
For units connected in parallel, when one of the power units is deactivated, then the enable in p7001 is withdrawn.
Description:
Displays the "active/inactive" state of a power unit component.
Values:
0:
Component inactive
1:
Component active
Dependency:
Refer to: p0105, p0125, p0897
Description:
Displays the version of the EPROM data of the power unit.
Dependency:
Refer to: r0147, r0157
p0124[0...n]
Power unit detection via LED / PU detection LED
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned8
Dynamic index:
PDS, p0120
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p0125[0...n]
Activate/de-activate power unit components / PU_comp act/de-act
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed:
C1(4), T
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
PDS, p0120
Func. diagram:
-
P-Group:
Data sets
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 2
1
r0126[0...n]
Power unit components active/inactive / PU comp act/inact
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
PDS, p0120
Func. diagram:
-
P-Group:
Data sets
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
-
r0127[0...n]
Power unit version EPROM data / PU EPROM version
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
PDS, p0120
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-