F
u
nct
ion
D
iag
ra
m
s
Safety Integrat
ed
2-
12
18
© Siemens AG
2007 All Rights Reserved
S
IN
A
MICS
S List Manua
l (
L
H1), 0
7
/2007
Fi
gure 2-1
0
6
2
848 – Exte
nde
d fun
c
ti
ons,
T
M
54F
co
nfigura
tio
n,
F
-DI/F
-DO te
st
- 2848 -
Function diagram
8
7
6
5
4
3
2
1
fp_2848_51_eng.vsd
DO: TM54F_MA, TM54F_SL
SINAMICS
19.06.07 V02.05.01
Safety Integrated - Extended Functions, TM54F Configuration, F-DI/F-DO Test
p10000 (12.00 ms)
Drive 1
p10011[0] (1)
Drive 2
p10011[1] (1)
Drive 3
p10011[2] (1)
Drive 4
p10011[3] (1)
Drive 5
p10011[4] (1)
Drive group assignment
SI FrcdCkProcTimer
0.00...8760.00 [h]
p10003 (8.00)
(0)
SI DI fcp F-DO
p10007
T
0
Drive group 1
Drive group 2
Drive group 3
Drive group 4
Drive 6
p10011[5] (1)
A35012
“Test stop activ“
F35013
“Test stop error“
A35014
“Test stop required“
Test F-DI
Test F-DO
SI F-DI enab test
p10041
SI test sens FS
p10046
Test stop
Restart timer (on successful test stop)
r10053.3 DI 23
r10053.0 DI 20
r10053.1 DI 21
r10053.2 DI 22
p10010[0]
Drive 1
p10010[1]
Drive 2
p10010[2]
Drive 3
p10010[3]
Drive 4
p10010[4]
Drive 5
p10010[5]
Drive 6
[2853.8]
[2853.8]
[2853.8]
[2853.8]