List of faults and alarms
Faults and Alarms
3-1601
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F08500 (A)
COMM BOARD: Monitoring time configuration expired
Drive object:
A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction:
A_INFEED: OFF1 (OFF2)
SERVO: OFF1 (OFF2, OFF3)
VECTOR: OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the configuration has expired.
Fault value (r0949, interpret decimal):
0: The transfer of the send-configuration data has been exceeded (time).
1: The transfer of the receive-configuration data has been exceeded (time).
Remedy:
Check communication line.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F08501 (A)
COMM BOARD: Monitoring time process data expired
Drive object:
A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction:
A_INFEED: OFF1 (OFF2)
SERVO: OFF1 (OFF2, OFF3)
VECTOR: OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The set monitoring time expired while transferring process data via COMM BOARD.
See also: p8840 (COMM BOARD monitoring time)
Remedy:
- check communications link.
- check the set monitoring time if the error persists.
See also: p8840 (COMM BOARD monitoring time)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F08502 (A)
COMM BOARD: Monitoring time sign-of-life expired
Drive object:
A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction:
A_INFEED: OFF1 (OFF2)
SERVO: OFF1 (OFF2, OFF3)
VECTOR: OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the sign-of-life counter has expired.
The connection to the COMM BOARD was interrupted.
Remedy:
- check communications link.
- check COMM BOARD.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A08504 (F)
COMM BOARD: Internal cyclic data transfer error
Drive object:
A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic actual and/or setpoint values were not transferred within the specified times.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.