Faults and Alarms
List of faults and alarms
3-1440
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F01036 (A)
ACX: Parameter back-up file missing
Drive object:
All objects
Reaction:
A_INFEED: NONE (OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When downloading the device parameterization, a parameter back-up file associated with a drive object cannot be
found. Neither a PSxxxyyy.ACX, a PSxxxyyy.NEW nor a PSxxxyyy.BAK parameter back-up file exists on the Com-
pactFlash card for this drive object.
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file name PSxxxyyy.ACX
yyy = 000 --> consistency back-up file
yyy = 001 ... 062 --> drive object number
yyy = 099 --> PROFIBUS parameter back-up file
Byte 2, 3, 4:
Only for internal Siemens troubleshooting.
Remedy:
If you have saved your project data using the commissioning software, carry out a new download for your project.
Save using the function "Copy RAM to ROM" or with p0977 = 1 so that all of the parameter files are again completely
written into the CompactFlash card.
If you have not saved the project data, then the system must be again commissioned for the first time.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01037 (A)
ACX: Re-naming the parameter back-up file not successful
Drive object:
All objects
Reaction:
A_INFEED: NONE (OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The re-naming after saving a parameter back-up file on the CompactFlash card or in the volatile memory was unsuc-
cessful.
One of the parameter back-up files to be re-named had the "read only" attribute. The parameter back-up files are
saved on the CompactFlash card in the directory \USER\SINAMICS\DATA.
It is possible that the CompactFlash card is defective.
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file names PSxxxyyy.* or CAxxxyyy.* or CCxxxyyy.*
yyy = 000 --> consistency back-up file
yyy = 099 --> PROFIBUS parameter back-up file PSxxx099.*
Byte 2: xxx in the file name PSxxxyyy.*
xxx = 000 --> data save started with p0977 = 1
xxx = 010 --> data save started with p0977 = 10
xxx = 011 --> data save started with p0977 = 11
xxx = 012 --> data save started with p0977 = 12
Byte 4, 3:
Only for internal Siemens troubleshooting.
Remedy:
- check whether one of the files to be overwritten has the attribute "read only" and change this file attribute into "writ-
able". Check all of the files (PSxxxyyy.*, CCxxxyyy.*, CAxxxyyy.*) that belong to drive yyy designated in the fault
value.
- replace the CompactFlash card.
Reaction upon A:
NONE
Acknowl. upon A:
NONE