List of parameters
Parameters
1-1017
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the PROFIsafe address of the Control Unit.
Dependency:
Refer to: p9810
Description:
Sets the signal source for the following functions on the Control Unit:
STO: Safe Torque Off / SH: Safe standstill
SBC: Safe Brake Control
SS1: Safe Stop 1 (time monitored)
Dependency:
Refer to: p9601
Note:
The following signal sources are permitted:
- fixed zero (standard setting).
- digital inputs DI 0 to DI 7 on the Control Unit 320 (CU320).
- digital inputs DI 0 to DI 3 on the Controller Extensions (CX32, NX10, NX15).
- digital inputs DI 0 to DI 3 on the Control Unit 310 (CU310).
It is not permitted to establish an interconnection to a digital input in the simulation mode.
For a parallel circuit configuration of n power units, the following applies:
p9620[0] = Signal source for power unit 1
...
p9620[n-1] = Signal source for power unit n
Description:
Sets the tolerance time to change over the safety-related inputs (SGE) on the Control Unit.
An SGE changeover is not simultaneously effective due to the different runtimes in the two monitoring channels.
After an SGE changeover, dynamic data is not subject to a data cross-check during this tolerance time.
Dependency:
Refer to: p9850
Note:
For a data cross-check between p9650 and p9850, a difference of one Safety monitoring clock cycle is tolerated.
The parameterized time is internally rounded-off to an integer multiple of the monitoring clock cycle.
SGE: Safety-related input (e.g. STO terminals)
p9610
SI PROFIsafe address (Control Unit) / SI PROFIsafe CU
SERVO, VECTOR
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0000 hex
FFFE hex
0000 hex
p9620[0...7]
BI: SI signal source for STO (SH)/SBC/SS1 (Control Unit) / SI S_srcSTO/SS1 CU
SERVO, VECTOR
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
-
Func. diagram:
2810
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p9650
SI SGE changeover tolerance time (Control Unit) / SI SGE_chg tol CU
SERVO, VECTOR
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
2810
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
2000.00 [ms]
500.00 [ms]