Parameters
List of parameters
1-120
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Enter the inductance of a filter connected at the power unit output.
Dependency:
The parameter is automatically pre-assigned when selecting a filter via p0230.
Refer to: p0230
Description:
Enters the capacitance of a sinusoidal filter connected at the power unit output.
Dependency:
The parameter is automatically pre-assigned when selecting a filter via (p0230).
Refer to: p0230
Note:
The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
Description:
Number of reactors connected at the power unit output.
Dependency:
Refer to: p0230
Caution:
If the number of motor reactors connected in series does not correspond to the parameter value, then this can
result in an unfavorable control behavior.
Note:
The parameter cannot be changed for chassis drive units and for p0230 = 1.
Description:
Sets the cooling type for booksize compact power units.
This therefore defines whether for these power units, the internal air cooling is shut down and instead, the "Cold-
Plate" cooling type is used.
Values:
0:
Air cooling internal
1:
Cold-Plate
Note:
For booksize compact power units, there is a 4 at the 5th position in the Order No.
The parameter is irrelevant for all other power unit types.
p0233
Power unit motor reactor / PU mot reactor
VECTOR
Can be changed:
C2(2), U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [mH]
1000.000 [mH]
0.000 [mH]
p0234
Power unit sinusoidal filter capacitance / PU sine filter C
VECTOR
Can be changed:
C2(2), U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [µF]
1000.000 [µF]
0.000 [µF]
p0235
Number of reactors connected in series / Qty L in series
VECTOR
Can be changed:
C2(1, 2)
Calculated:
-
Access level:
1
Data type:
Unsigned8
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1 3
1
p0249
Power unit cooling type / PU cool type
SERVO, S_INF,
VECTOR
Can be changed:
C2(1, 2)
Calculated:
-
Access level:
4
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
0