List of parameters
Parameters
1-337
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Refer to: p0840, p0857, p1267
Refer to: F30003
Danger:
If the automatic restart is activated (p1210 > 1) if there is an ON command (refer to p0840), the drive is powered-up
as soon as any fault messages that are present can be acknowledged. This also occurs after the line supply returns
or the CU board boots if the DC link voltage is again present or the feedback of the line supply infeed (refer to
p0864) is again available. This automatic power-up sequence can only be interrupted by withdrawing the ON com-
mand.
Caution:
A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
For p1210 > 1, the infeed is automatically started.
Note:
p1210 = 4:
An automatic restart is only executed if fault F06200 has occurred. If additional faults are present, then these faults
are also acknowledged and when successful, starting continues. If the 24 V CU power supply fails, then this is inter-
preted as a line supply failure.
p1210 = 6:
An automatic restart is carried out if any fault has occurred.
p1210 = 1:
Faults that are present are automatically acknowledged. If new faults occur after a successful fault acknowledge-
ment, then these are also automatically acknowledged again. A minimum time of p1212 + 1s must expire between
a successful fault acknowledgement and a fault re-occurring if the signal ON/OFF1 (control word 1, bit 0) is at a
HIGH signal level. If the signal ON/OFF1 is at a LOW signal level, then the time between a successful fault
acknowledgement and a new fault must be at least 1s.
For p1210 = 1, fault F07320 is not generated if the acknowledgement attempt was not successful, for example, due
to frequently occurring faults.
Description:
Sets the automatic restart mode (AR).
Values:
0:
Disables automatic restart
1:
Acknowledges all faults without restarting
4:
Restart after power failure without additional start attempts
6:
Restart after fault with additional start attempts
Dependency:
The automatic restart requires an active ON command, e.g. that is available at a digital input.
If, for p1210 > 1, there is no active ON command, then the automatic restart is interrupted.
When using an Advanced Operator Panel (AOP) in the LOCAL Mode, then there is no automatic restart.
Refer to: p0840, p0857, p1267
Refer to: F30003
Danger:
If the automatic restart is activated (p1210 > 1) if there is an ON command (refer to p0840), the drive is powered-up
as soon as any fault messages that are present can be acknowledged. This also occurs after the line supply returns
or the CU board boots if the DC link voltage is again present or the feedback of the line supply infeed (refer to
p0864) is again available. This automatic power-up sequence can only be interrupted by withdrawing the ON com-
mand.
Caution:
A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
For p1210 > 1, the motor is automatically started.
Note:
For brief line supply failures, the motor shaft can still be rotating when restarting. In order to restart while the motor
shaft is still rotating, the "flying restart" function should be activated using p1200.
p1210 = 4:
An automatic restart is only carried out if Fault F30003 occurred at the Motor Module or a high signal is present at
the binector input p1208[1]. If additional faults are present, then these faults are also acknowledged and when suc-
cessful, starting continues. If the 24 V CU power supply fails, then this is interpreted as a line supply failure.
p1210 = 6:
An automatic restart is carried out if any fault has occurred or there is a high signal at binector input p1208[0].
p1210
Automatic restart, mode / AR mode
SERVO, VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 6
0