Parameters
List of parameters
1-372
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard charac-
teristic is used that contains the rated motor operating point.
Refer to: p1300, p1310, p1311, p1321, p1322, p1323, p1324, p1325, p1326, p1327
Note:
Linear interpolation is carried out between the points 0 Hz / p1310, p1320 / p1321 ... p1326 / p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable V/Hz characteristic.
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1310, p1311, p1320, p1322, p1323, p1324, p1325, p1326, p1327
Note:
Linear interpolation is carried out between the points 0 Hz / p1310, p1320 / p1321 ... p1326 / p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable V/Hz characteristic.
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the second point along the characteristic.
Dependency:
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard charac-
teristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1323, p1324, p1325, p1326, p1327
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the second point along the characteristic.
Dependency:
Refer to: p1310, p1311, p1320, p1321, p1322, p1324, p1325, p1326, p1327
p1321[0...n]
V/f control programmable characteristic voltage 1 / Uf char U1
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6300
P-Group:
V/f open-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [Vrms]
10000.0 [Vrms]
0.0 [Vrms]
p1322[0...n]
V/f control programmable characteristic frequency 2 / Uf char f2
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6300
P-Group:
V/f open-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Hz]
3000.00 [Hz]
0.00 [Hz]
p1323[0...n]
V/f control programmable characteristic voltage 2 / Uf char U2
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_ALL
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
6300
P-Group:
V/f open-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [Vrms]
10000.0 [Vrms]
0.0 [Vrms]