Parameters
List of parameters
1-462
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Activates current setpoint filters 1 to 4.
Dependency:
The current setpoint filters are parameterized with p1656 to p1676.
Note:
If not all of the filters are required, then the filters should be used consecutively starting from filter 1.
Description:
Activates current setpoint filters 1 to 2.
Dependency:
The current setpoint filters are parameterized with p1656 to p1666.
Note:
If not all of the filters are required, then the filters should be used consecutively starting from filter 1.
Description:
Sets the current setpoint filter 1 as low pass (PT2) or as extended general 2nd-order filter.
Values:
1:
Low pass: PT2
2:
General 2nd-order filter
Dependency:
The current setpoint filters are parameterized with p1656 to p1676.
Note:
For an extended general 2nd order filter, by inserting the same natural frequency in both the numerator and in the
denominator, i.e. bandstop frequency, a bandstop filter is implemented. If the numerator damping of zero is
selected, the bandstop frequency is completely suppressed. The denominator damping can be determined from the
equation for the 3 dB bandwidth: f_3dB bandwidth = 2 * D_denominator * f_bandstop frequency
p1656[0...n]
Activates current setpoint filter / I_set_filt active
SERVO
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Unsigned16
Dynamic index:
DDS, p0180
Func. diagram:
5710
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0001
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Filter 1
Active
Inactive
-
01
Filter 2
Active
Inactive
-
02
Filter 3
Active
Inactive
-
03
Filter 4
Active
Inactive
-
p1656[0...n]
Activates current setpoint filter / I_set_filt active
VECTOR (n/M)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
DDS, p0180
Func. diagram:
6710
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- -
0001
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Filter 1
Active
Inactive
-
01
Filter 2
Active
Inactive
-
p1657[0...n]
Current setpoint filter 1 type / I_set_filt 1 Typ
SERVO, VECTOR
(n/M)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Integer16
Dynamic index:
DDS, p0180
Func. diagram:
5710, 6710
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
1 2
1