![Siemens SINAMICS S Series List Manual Download Page 1000](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271000.webp)
Parameters
List of parameters
1-1000
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
[3] = Limit value SLP4
Dependency:
Refer to: p9532, p9561, p9563
Refer to: C01714
Note:
A change only becomes effective after a POWER ON.
SLS: Safely-Limited Speed / SG: Safely reduced speed
Description:
Sets the limit values for the function "Safely-Limited Speed" (SLS).
Index:
[0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLP4
Dependency:
Refer to: p9532, p9561, p9563
Refer to: C01714
Note:
A change only becomes effective after a POWER ON.
SLS: Safely-Limited Speed / SG: Safely reduced speed
Description:
Sets the override factor for the limit value for SLS2 and SLS4 for the function "Safely-Limited Speed" (SLS).
Index:
[0] = SLS (SG) override factor 0
[1] = SLS (SG) override factor 1
[2] = SLS (SG) override factor 2
[3] = SLS (SG) override factor 3
[4] = SLS (SG) override factor 4
[5] = SLS (SG) override factor 5
[6] = SLS (SG) override factor 6
[7] = SLS (SG) override factor 7
[8] = SLS (SG) override factor 8
[9] = SLS (SG) override factor 9
[10] = SLS (SG) override factor 10
[11] = SLS (SG) override factor 11
[12] = SLS (SG) override factor 12
[13] = SLS (SG) override factor 13
[14] = SLS (SG) override factor 14
[15] = SLS (SG) override factor 15
Dependency:
Refer to: p9501, p9531
Note:
The actual override factor for SLS2 and SLS4 is selected using the safety-relevant inputs (SGE).
A change only becomes effective after a POWER ON.
SLS: Safely-Limited Speed / SG: Safely reduced speed
p9531[0...3]
SI motion SLS (SG) limit values (Control Unit) / SI Mtn SLS lim CU
SERVO (Safety rot),
VECTOR (Safety rot)
Can be changed:
C2
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [RPM]
1000000.00 [RPM]
2000.00 [RPM]
p9532[0...15]
SI motion SLS (SG) override factor (Control Unit) / SI Mtn SLS over
SERVO, VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Safety Integrated
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [%]
100.000 [%]
100.000 [%]