![Siemens SINAMICS S Series List Manual Download Page 1732](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271732.webp)
Faults and Alarms
List of faults and alarms
3-1732
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F35836
TM DRIVE-CLiQ: Send error for DRIVE-CLiQ data
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the Control Unit and the Terminal Module involved.
Data were not able to be sent.
Fault value (r0949, interpret hexadecimal):
41: Telegram type does not match send list.
Remedy:
Carry out a POWER ON.
F35837
PTM DRIVE-CLiQ: Component fault
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component involved. Faulty hardware cannot be excluded.
Fault value (r0949, interpret hexadecimal):
20: Error in the telegram header.
23: Receive error: The telegram buffer memory contains an error.
42: Send error: The telegram buffer memory contains an error.
43: Send error: The telegram buffer memory contains an error.
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
F35845
TM DRIVE-CLiQ: Cyclic data transfer error
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the Control Unit and the Terminal Module (TM)
involved.
Fault value (r0949, interpret hexadecimal):
0B: Synchronization error during alternating cyclic data transfer.
Remedy:
Carry out a POWER ON.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
F35850
TM: Internal software error
Drive object:
All objects
Reaction:
A_INFEED: OFF1 (NONE, OFF2)
SERVO: OFF1 (NONE, OFF2, OFF3)
VECTOR: OFF1 (NONE, OFF2, OFF3)
Acknowledge:
POWER ON
Cause:
An internal software error in the Terminal Module (TM) has occurred.
Fault value (r0949, interpret decimal):
1: Background time slice is blocked.
2: Checksum over the code memory is not OK.
Remedy:
- replace the Terminal Module (TM).
- if required, upgrade the firmware in the Terminal Module.
- contact the Hotline.