![Siemens SINAMICS S Series List Manual Download Page 525](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_1265427525.webp)
List of parameters
Parameters
1-525
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note:
For high moments of inertia, it is practical to scale the runtime of the calibration higher.
Description:
Sets the reference quantity for the frequency.
All frequencies specified as relative value are referred to this reference quantity.
The reference quantity in this parameter corresponds to 100% or 4000 hex or 4000 0000 hex.
The following applies: Reference frequency (in Hz)
Description:
Sets the reference quantity for speed and frequency.
All speeds or frequencies specified as relative value are referred to this reference quantity.
The reference quantity in this parameter corresponds to 100% or 4000 hex or 4000 0000 hex.
The following applies: Reference frequency (in Hz) = reference speed (in (RPM) / 60)
Dependency:
Refer to: p0500, p2001, p2002, p2003, r2004
Note:
For the automatic calculation (p0340 = 1, p3900 > 0) an appropriate pre-assignment is only made if the parameter
is not inhibited from being overwritten using p0573 = 1.
If a BICO interconnection is established between different physical quantities, then the particular reference quanti-
ties are used as internal conversion factor.
Example 1:
The signal of an analog input (e.g. r4055[0]) is connected to a speed setpoint (e.g. p1070[0]). The actual percent-
age input value is cyclically converted into the absolute speed setpoint using the reference speed (p2000).
Example 2:
The setpoint from PROFIBUS (r2050[1]) is connected to a speed setpoint (e.g. p1070[0]). The current input value is
cyclically converted into a percentage value via the pre-specified normalization 4000 hex. This percentage value is
converted to the absolute speed setpoint via reference speed (p2000).
Description:
Sets the reference quantity for velocity and frequency.
All velocities or frequencies specified as relative value are referred to this reference quantity.
The reference quantity in this parameter corresponds to 100% or 4000 hex or 4000 0000 hex.
The following applies: Reference frequency (in Hz) = reference velocity (in (m/min) / 60)
Dependency:
Refer to: p0500, p2001, p2002, p2003, r2004
p2000
Reference frequency / Ref freq
A_INF, B_INF,
S_INF
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.10 [Hz]
1000.00 [Hz]
50.00 [Hz]
p2000
Reference speed reference frequency / Ref_n Ref_f
SERVO
Can be changed:
T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
6.00 [RPM]
210000.00 [RPM]
3000.00 [RPM]
p2000
Reference velocity, reference frequency / Ref_v Ref_f
SERVO (Lin)
Can be changed:
T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.60 [m/min]
600.00 [m/min]
120.00 [m/min]