List of parameters
Parameters
1-549
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays how often the sign-of-life from the clock synchronous PROFIBUS/PROFINET master failed.
An appropriate fault is output when the tolerance, specified in p0925, is exceeded.
Dependency:
Refer to: F01912
Description:
Activates an automatic warm restart after changing the DP clock cycle has been changed.
p2066 = 0:
An attempt to change the DP clock cycle is rejected, and Alarm A01902 is output with alarm value = 9. In order that
the DP clock cycle becomes effective, a warm restart or POWER ON must be carried out.
p2066 = 1:
When the DP clock cycle is changed, an automatic warm restart is initiated (p0009 = 30, p0976 = 3). After booting
the modified DP clock cycle becomes effective. The automatic warm restart is only carried out if for all of the drives
the pulses have been canceled. Otherwise p0009 = 30 cannot be executed and an attempt to change the DP clock
cycle is rejected as for p2066 = 0.
Dependency:
Refer to: A01902
Description:
Displays the PROFIBUS address of the sender from which the process data (PZD) is received.
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Note:
IF1: Interface 1
Value range:
0 - 125: Bus address of the sender
255: Not occupied
r2065
PROFIdrive master sign-of-life, diagnostics / PD mast-SoL diag
CU_CX32, CU_S,
SERVO, TM41, VEC-
TOR (n/M)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
2410
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
p2066
SYNC automatic warm restart / SYNC warm restart
CU_CX32, CU_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
0
Min Max
Factory
setting
0 1
0
r2074[0...4]
IF1 PROFIdrive diagnostics bus address PZD receive / IF1diag addr recv
A_INF, B_INF,
CU_CX32, CU_S,
S_INF, TB30,
TM15DI_DO, TM31
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-