List of parameters
Parameters
1-707
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
If the line supply angle (angle between the line supply phases) suddenly changes by this value, then a phase failure
is assumed. The pulses are then inhibited for 10 ms.
Dependency:
Refer to: A06205
Description:
Displays the line supply voltage at the input terminals of the line filter in alpha/beta components.
Index:
[0] = Alpha component
[1] = Beta component
Note:
The input terminals of the line filter form, for infeeds, the connection point of the Voltage Sensing Module (VSM) to
measure the line supply voltage.
For operation with VSM (p3400.5 = 1), the following applies:
The voltage measured values r3661 and r3662, transformed into the alpha/beta system are displayed in r3468.
For sensorless operation without VSM (p3400.5 = 0), the following applies:
The estimated values of the voltages from the line supply model of the PLL transformed into the alpha/beta system
are displayed in r3468.
Description:
Calibration value for the RC filter of the zero crossover detection of the line supply voltage in the power unit.
For p3469 = 0, a new calibration is carried out at the next identification run with p3410 = 4 or p3410 = 5.
Note:
The calibration value is saved in the EEPROM of the power unit (not on the CompactFlash card), as it involves a
characteristic/feature of the power unit.
Description:
Displays the active current requirement due to the line filter.
Dependency:
Refer to: r0038, p0221, p0222
p3463
Infeed, line angle change, phase failure detection / INF Phi phase fail
A_INF, S_INF
Can be changed:
T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-180.0 [°]
180.0 [°]
15.0 [°]
r3468[0...1]
Infeed voltage alpha/beta line filter / INF V a/b filter
A_INF, S_INF
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [V]
- [V]
- [V]
p3469[0...n]
Latch delay time correction, zero crossover detection / t_latch corr PLL
A_INF, S_INF
Can be changed:
T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
PDS, p0120
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-10000.0 [µs]
10000.0 [µs]
0.0 [µs]
r3470
Infeed active current filter / INF I_act filter
A_INF
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
6_2
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]