List of parameters
Parameters
1-145
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the correction factor for the stall force at a 600 V DC link voltage.
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Sets the optimum load angle for synchronous motors with reluctance torque (e.g. 1FE ... motors).
This parameter has no significance for induction motors.
SERVO: The load angle is measured at 150% rated motor current.
VECTOR: The load angle is measured at the rated motor current.
Dependency:
Refer to: r1947
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
For synchronous motors without reluctance torque, a angle of 90 degrees must be set.
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Sets the reluctance torque constant for synchronous motors with reluctance torque (e.g. 1FE ... motors).
This parameter has no significance for induction motors.
Dependency:
Refer to: r1939
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
For synchronous motors without reluctance torque, the value 0 must be set.
The parameter is automatically preset for motors from the motor list (p0301).
p0326[0...n]
Motor stall force correction factor / Mot F_stall_corr
SERVO (Lin)
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
REL, FEM
Expert list:
1
Min Max
Factory
setting
5 [%]
300 [%]
60 [%]
p0327[0...n]
Optimum motor load angle / Mot phi_load opt
SERVO, VECTOR
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
5722
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
ASM, REL, FEM
Expert list:
1
Min Max
Factory
setting
0.0 [°]
135.0 [°]
90.0 [°]
p0328[0...n]
Motor reluctance torque constant / Mot kT_reluctance
SERVO, VECTOR
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
ASM, REL, FEM
Expert list:
1
Min Max
Factory
setting
-1000.00 [mH]
1000.00 [mH]
0.00 [mH]