List of parameters
Parameters
1-727
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the alarm threshold for the KTY temperature sensor of the Voltage Sensing Module (VSM) to monitor the line
filter temperature.
Prerequisite:
A KTY84 sensor is connected and p3665 is set to 2.
Dependency:
Refer to: p3665
Refer to: F34207
Description:
Sets the alarm threshold for the KTY temperature sensor of the Voltage Sensing Module (VSM) to monitor the line
filter temperature.
Prerequisite:
A KTY84 sensor is connected and p3665 is set to 2.
Dependency:
Refer to: p3665
Refer to: F34207
Description:
Sets the shutdown threshold for the KTY temperature sensor of the VSM to monitor the line filter temperature.
Dependency:
Refer to: p3667
Refer to: A34211
Description:
Sets the shutdown threshold for the KTY temperature sensor of the VSM to monitor the line filter temperature.
Dependency:
Refer to: p3667
Refer to: A34211
p3667
VSM line filter overtemperature alarm threshold / VSMfilt_T A_thresh
A_INF, S_INF
Can be changed:
T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9886
P-Group:
-
Units group:
21_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 [°C]
301 [°C]
150 [°C]
p3667[0...n]
VSM line filter overtemperature alarm threshold / VSMfilt_T A_thresh
VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
p0150
Func. diagram:
9886
P-Group:
-
Units group:
21_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [°C]
301.00 [°C]
150.00 [°C]
p3668
VSM line filter overtemperature shutdown threshold / VSM filt_T F_thres
A_INF, S_INF
Can be changed:
T
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9886
P-Group:
-
Units group:
21_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 [°C]
301 [°C]
180 [°C]
p3668[0...n]
VSM line filter overtemperature shutdown threshold / VSM filt_T F_thres
VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
p0150
Func. diagram:
9886
P-Group:
-
Units group:
21_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [°C]
301.00 [°C]
180.00 [°C]