List of faults and alarms
Faults and Alarms
3-1503
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A01955
CU DRIVE-CLiQ: Synchronization DO not completed
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
After the drive system is powered-up, the synchronization between the basic clock cycle, DRIVE-CLiQ clock cycle
and application clock cycle was started but was not completed within the selected time (tolerance).
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
Carry out a POWER ON (power off/on) for all components of the DO.
A02000
Function generator: Start not possible
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The function generator has already been started.
Remedy:
Stop the function generator and restart again if necessary.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4800 (Function generator control)
A02005
Function generator: Drive does not exist
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive object specified for connection does not exist.
See also: p4815 (Function generator drive number)
Remedy:
Use the existing drive object with the corresponding number.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4815 (Function generator drive number)
A02006
Function generator: No drive specified for connection
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
No drive specified for connection in p4815.
See also: p4815 (Function generator drive number)
Remedy:
At least one drive to be connected must be specified in p4815.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4815 (Function generator drive number)
A02007
Function generator: Drive not SERVO / VECTOR
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive object specified for connection is not a SERVO / VECTOR.
See also: p4815 (Function generator drive number)