Parameters
List of parameters
1-604
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays the second status word for monitoring functions.
Note:
Re bit 10:
The force threshold value 1 is set in p2174.
Re bit 07:
For servo drives, bit 07 is not used and is always inactive.
Description:
Displays the third status word for monitoring functions.
Note:
Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141.
Re bit 11:
The torque threshold value 2 is set in p2194.
Description:
Displays the third status word for monitoring functions.
r2198.4...12
CO/BO: Status word monitoring 2 / ZSW monitor 2
SERVO (Lin)
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1530, 2536
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
04
|n_set| < p2161
Yes
No
8010
05
n_set > 0
Yes
No
8010
06
Motor locked
Yes
No
8012
07
Motor stalled
Yes
No
8012
10
Force setpoint < force threshold value 1
Yes
No
8012
11
Load monitoring signals an alarm
Yes
No
8013
12
Load monitoring signals a fault condition
Yes
No
8013
r2199.0...11
CO/BO: Status word monitoring 3 / ZSW monitor 3
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1530, 2536
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
|n_act| < speed threshold value 3
Yes
No
8010
01
f or n comparison value reached or
exceeded
Yes
No
8010
04
Speed setp - act val deviation in tolerance
t_on
Yes
No
8010
05
Ramp-up/ramp-down completed
Yes
No
8010
06
Current below the zero current threshold
Yes
No
-
11
Torque utilization < torque threshold value 2 Yes
No
8012
r2199.0...11
CO/BO: Status word monitoring 3 / ZSW monitor 3
SERVO (Lin)
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1530, 2536
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-