List of parameters
Parameters
1-149
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter influences the thermal 3-mass motor model.
1LA1 and 1LA8 motors are characterized by the fact that they have an internal rotor fan. This "internal cooling" lies
within the motor frame and is not visible. Air is not directly exchanged with the motor ambient air.
The parameter is automatically preset for motors from the motor list (p0301).
1LA7 motors, frame size 56 are operated without fan.
Description:
Displays the rated frequency of the motor.
For p0310 > 0, this value is displayed.
Dependency:
Refer to: p0311, p0314
Note:
For p0310 = 0 or for synchronous motors, the rated motor frequency r0336 is calculated from the rated speed and
the pole pair number.
For p0310 > 0, this value is displayed (not for synchronous motors).
Description:
Displays the rated EMF of the motor.
Note:
EMF: Electromagnetic force
Description:
Displays the rated EMF of the motor.
Note:
EMF: Electromagnetic force
Description:
Sets the motor limit current for synchronous motors (for a 600 V DC link voltage).
Using this current, the maximum torque is achieved at the rated speed (voltage limit characteristic).
r0336[0...n]
Rated motor frequency actual / Mot f_rated act
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
r0337[0...n]
Rated motor EMF / Mot EMF_rated
SERVO, VECTOR
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [Vrms]
- [Vrms]
- [Vrms]
r0337[0...n]
Rated motor EMF / Mot EMF_rated
SERVO (Lin)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
- [Vrms s/m]
- [Vrms s/m]
- [Vrms s/m]
p0338[0...n]
Motor limit current / Mot I_limit
SERVO
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
ASM, REL, FEM
Expert list:
1
Min Max
Factory
setting
0.00 [Arms]
10000.00 [Arms]
0.00 [Arms]