Parameters
List of parameters
1-252
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Bit 10 = 0: No master control by PLC
Bit 10 = 1: Master control by PLC
This bit is used to initiate a response for the drives when the control fails (F07220). If there is not control available,
then BI: p0854 should be set to a 1 signal.
Description:
Sets the signal source for the command "unconditionally open holding brake".
Dependency:
Refer to: p0858
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The signal via BI: p0858 (unconditionally close holding brake) has a higher priority than via BI: p0855 (uncondition-
ally open holding brake).
Description:
Sets the signal source for the command "enable speed controller" (r0898.12).
0 signal: Set the I component and speed controller output to zero.
1 signal: Enable speed controller.
Dependency:
Refer to: r0898
Note:
If "enable speed controller" is withdrawn, then if a brake being used, then it is closed.
If "speed controller enable" is withdrawn, the pulses are not canceled.
Description:
Sets the signal source for the command "enable speed controller" (r0898.12).
0 signal: Set the I component and speed controller output to zero.
1 signal: Enable speed controller.
Dependency:
Refer to: r0898
Note:
If "enable speed controller" is withdrawn, then if a brake being used, then it is closed.
If "speed controller enable" is withdrawn, the pulses are not canceled.
p0855[0...n]
BI: Unconditionally release holding brake / Uncond open brake
SERVO, VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
2501, 2701,
2707
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p0856[0...n]
BI: Enable speed controller / Enable n_ctrl
SERVO, VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
2501, 2701,
2707
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p0856[0...n]
BI: Enable velocity controller / Enable v_ctrl
SERVO (Lin)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
2501, 2701,
2707
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
1