List of parameters
Parameters
1-631
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the signal source for the position setpoint of the position controller.
Dependency:
Refer to: r2665
Note:
When the function module "basic positioner" (r0108.4 = 1) is activated, the following BICO interconnection is estab-
lished: BI: p2530 = r2665
Description:
Sets the signal source for the velocity setpoint of the position controller.
Dependency:
Refer to: r2666
Note:
When the function module "basic positioner" (r0108.4 = 1) is activated, the following BICO interconnection is estab-
lished: BI: p2531 = r2666
Description:
Sets the signal source for the position actual value of the position controller.
Dependency:
Refer to: r2521
Description:
Sets the time constant for the position setpoint filter (PT1).
Note:
The effective Kv factor (position loop gain) is reduced with the filter. This allows a softer control behavior with
improved tolerance with respect to noise/disturbances.
Applications:
- reduces the pre-control dynamic response.
- jerk limiting.
p2530
CI: LR position setpoint / s_set
SERVO (Pos ctrl),
VECTOR (Pos ctrl)
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Integer32
Dynamic index:
-
Func. diagram:
4015
P-Group:
Closed loop position control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p2531
CI: LR velocity setpoint / v_set
SERVO (Pos ctrl),
VECTOR (Pos ctrl)
Can be changed:
T
Calculated:
-
Access level:
1
Data type:
Unsigned32 / Integer32
Dynamic index:
-
Func. diagram:
4015
P-Group:
Closed loop position control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p2532
CI: LR position actual value / s_act
SERVO (Pos ctrl),
VECTOR (Pos ctrl)
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Integer32
Dynamic index:
-
Func. diagram:
4015
P-Group:
Closed loop position control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
2521[0]
p2533[0...n]
LR position setpoint filter, time constant / s_set_filt T
SERVO (Pos ctrl),
VECTOR (Pos ctrl)
Can be changed:
U, T
Calculated:
-
Access level:
1
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
4015
P-Group:
Closed loop position control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [ms]
1000.00 [ms]
0.00 [ms]