List of parameters
Parameters
1-891
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the normalized proportional gain for the circulating current controller.
Note:
A value of 100 % corresponds to the basic setting derived from loop control parameters (p3421, p3622).
Description:
Sets the proportional gain for the circulating current controller.
The parameter is pre-set to the cable resistance.
Description:
Sets the normalized integral time of the circulating current controller.
Note:
A value of 100 % corresponds to the basic setting derived from the controller sampling time p0115[0].
The integral component of the controller is de-activated with p7037 = 0.
Description:
Sets the integral time of the circulating current controller.
The parameter is referred to the current controller sampling time (p0115[0]).
Dependency:
Refer to: p0115
p7036
Infeed par_cct circulating current controller proportional gain / Circ_I Kp
A_INF (Parallel),
S_INF (Parallel)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00000 [%]
1000.00000 [%]
100.00000 [%]
p7036[0...n]
Par_circuit circulating current control proportional gain / Circ_I Kp
VECTOR (Parallel)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00000 [Ohm]
20.00000 [Ohm]
0.00000 [Ohm]
p7037
Infeed par_cct circulating current control integral time / I_circ Tn
A_INF (Parallel),
S_INF (Parallel)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
100000.0 [%]
100.0 [%]
p7037[0...n]
Par_circuit circulating current control integral time / I_circ Tn
VECTOR (Parallel)
Can be changed:
U, T
Calculated:
CALC_MOD_CON
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Modulation
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
2.0 1000.0
4.0