![Siemens SINAMICS S Series List Manual Download Page 1649](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271649.webp)
List of faults and alarms
Faults and Alarms
3-1649
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Alarm value (r2124, interpret decimal):
Low word: Signal level, track C (16 bits with sign).
High word: Signal level, track D (16 bits with sign).
A signal level of 500 mV corresponds to the numerical value 5333 hex = 21299 dec.
See also: p0491 (Motor encoder fault response ENCODER)
Remedy:
- check that the encoder cables are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
- check the Hall sensor box
Reaction upon F:
A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (ENCODER, IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
VECTOR: NONE (ENCODER, IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
N31415 (F, A)
Encoder 1: Amplitude alarm track A or B (A^2 + B^2)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The amplitude (A^2 + B^2) of track A or B is not within the tolerance bandwidth.
SMC20:
The nominal signal level is at 500 mV (500 mV -25 % / +20 %). The response threshold is < 300 mV.
SMC10:
The nominal signal level is at 2900 mV (2.0 Vrms). The response threshold is < 1414 mV (1.0 Vrms).
Alarm value (r2124, interpret decimal):
Low word:
Amplitude square root(A*A + B*B).
SMC20:
A signal level of 500 mV peak value corresponds to the numerical value 299A hex = 10650 dec.
SMC10:
A signal level of 2900 mV peak value corresponds to the numerical value 3333 hex = 13107 dec.
High word:
Angle 0 to 65535 corresponds to 0 to 360 degrees of the fine position. Zero degrees is at the negative zero crossover
of track B.
See also: p0491 (Motor encoder fault response ENCODER)
Remedy:
- check the speed range, frequency characteristic (amplitude characteristic) of the measuring equipment is not suf-
ficient for the speed range.
- check that the encoder cables are routed in compliance with EMC.
- check the plug connections.
- replace the encoder or encoder cable.
- check the Sensor Module (e.g. contacts).
- dirty code disk
- aged lighting system.
Reaction upon F:
A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (ENCODER, IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
VECTOR: NONE (ENCODER, IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowl. upon F:
IMMEDIATELY
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A31418 (F, N)
Encoder 1: Speed difference per sampling rate exceeded
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
For an HTL/TTL encoder, the speed difference between two sampling cycles has exceeded the value in p0492.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.