Parameters
List of parameters
1-574
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency:
Refer to: p3110, p3111, p3112
Refer to: F07862
Note:
An external fault is triggered with a 1/0 signal.
If this fault is output at the Control Unit, then it is transferred to all existing drive objects.
Description:
Sets the signal source for external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p3110, p3111, p3112
Refer to: F07862
Note:
An external fault is triggered with a 1/0 signal.
If this fault is output at the Control Unit, then it is transferred to all existing drive objects.
Description:
Displays the system runtime in milliseconds when the fault was removed.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2114, r2130, r2133, r2136
Notice:
The time comprises r2136 (days) and r2109 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
Description:
This parameter is identical to r2122.
p2108[0...n]
BI: External fault 3 / External fault 3
A_INF, B_INF,
SERVO, S_INF,
TM41, VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
2546
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
1
r2109[0...63]
Fault time removed in milliseconds / t_flt resolved ms
All objects
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
1750, 8060
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
r2110[0...63]
Alarm number / Alarm number
All objects
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
8065
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-