List of parameters
Parameters
1-235
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
The normalization characteristic for the test sockets is defined using two points. This parameter specifies the x
coordinate (percentage) of the second point on the characteristic.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Can only be set when p0776 = 99.
Refer to: p0777, p0778, p0780, r0786
Note:
The value 100.00 % corresponds to 4.98 V.
Description:
The normalization characteristic for the test sockets is defined using two points. This parameter specifies the y
coordinate (output voltage) of the second point on the characteristic.
Index:
[0] = T0
[1] = T1
[2] = T2
Dependency:
Can only be set when p0776 = 99.
Refer to: p0777, p0778, p0779, r0786
Description:
Sets an additional offset for the test sockets.
Index:
[0] = T0
[1] = T1
[2] = T2
Description:
Sets the limit for a signal to be output via test sockets.
p0779[0...2]
Test socket characteristic value x2 / Test skt char x2
CU_CX32, CU_S
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8134
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-100000.00 [%]
427.9E9 [%]
100.00 [%]
p0780[0...2]
Test socket characteristic value y2 / Test skt char y2
CU_CX32, CU_S
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8134
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.00 [V]
4.98 [V]
4.98 [V]
p0783[0...2]
Test sockets offset / Test skt offset
CU_CX32, CU_S
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8134
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-4.98 [V]
4.98 [V]
0.00 [V]
p0784[0...2]
Test socket limit on/off / TestSktLim on/off
CU_CX32, CU_S
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Integer16
Dynamic index:
-
Func. diagram:
8134
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 1
0