List of faults and alarms
Faults and Alarms
3-1603
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A08520 (F)
COMM BOARD: Non-cyclic channel error
Drive object:
A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory or the buffer status of the non-cyclic channel has an error.
Alarm value (r2124, interpret decimal):
0: Error in the buffer status.
1: Error in the memory.
Remedy:
Check communication line.
Reaction upon F:
A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A08526 (F)
COMM BOARD: No cyclic connection
Drive object:
A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is no cyclic connection to the control.
Remedy:
Establish the cyclic connection and activate the control with cyclic operation.
For PROFINET, check the parameters "Name of Station" and "IP of Station" (r61000, r61001).
Reaction upon F:
NONE (OFF1)
Acknowl. upon F:
IMMEDIATELY
A08530 (F)
COMM BOARD: Message channel error
Drive object:
A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory or the buffer status of the message channel has an error.
Alarm value (r2124, interpret decimal):
0: Error in the buffer status.
1: Error in the memory.
Remedy:
Check communication line.
Reaction upon F:
A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
A08550
PZD Interface Hardware assignment error
Drive object:
A_INF, B_INF, CU_LINK, CU_S, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41,
TM54F_MA, TM54F_SL, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The assignment of the hardware to the PZD interface has been incorrectly parameterized.
Alarm value (r2124, interpret decimal):
1: Only one of the two indices is not equal to 99 (automatic).
2: Both PZD interfaces are assigned to the same hardware.
3: Assigned COMM BOARD missing.
4: CBC10 is assigned to interface 1.
See also: p8839 (PZD interface hardware assignment)
Remedy:
Correct the parameterization (p8839).