Parameters
List of parameters
1-306
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the signal source for jog 1.
Recommend.:
When the signal source is set, this does not trigger a response - but only a signal change of the source.
Dependency:
Refer to: p0840, p1058
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power-up can also be used to power-down again.
Description:
Sets the signal source for jog 2.
Recommend.:
When the signal source is set, this does not trigger a response - but only a signal change of the source.
Dependency:
Refer to: p0840, p1059
Notice:
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power-up can also be used to power-down again.
Description:
Sets the speed/velocity for jog 1. Jogging is level-triggered and allows the motor to be incrementally moved.
Dependency:
Refer to: p1055, p1056
Description:
Sets the speed/velocity for jog 1. Jogging is level-triggered and allows the motor to be incrementally moved.
Dependency:
Refer to: p1055, p1056
p1055[0...n]
BI: Jog bit 0 / Jog bit 0
SERVO (Extended
setp), VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
2501, 2610,
3030
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1056[0...n]
BI: Jog bit 1 / Jog bit 1
SERVO (Extended
setp), VECTOR
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dynamic index:
CDS, p0170
Func. diagram:
2501, 2610,
3030
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p1058[0...n]
Jog 1 speed setpoint / Jog 1 n_set
SERVO (Extended
setp), VECTOR
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
3030
P-Group:
Setpoints
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-210000.000 [RPM]
210000.000 [RPM]
0.000 [RPM]
p1058[0...n]
Jog 1 velocity setpoint / Jog 1 n_set
SERVO (Extended
setp, Lin)
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
3030
P-Group:
Setpoints
Units group:
4_1
Unit selection:
p0505
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-1000.000 [m/min]
1000.000 [m/min]
0.000 [m/min]