List of parameters
Parameters
1-595
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the delay time for the message "Motor locked" (BO: r2198.6).
If "Motor locked" is identified within this time, then ZSW2.6 is set and an appropriate fault is output.
Dependency:
Refer to: p0500, p2175, r2198
Description:
Sets the delay time for the message "Motor stalled" (BO: r2198.7).
If "Motor stalled" is identified within this time, then ZSW2.7 is set and an appropriate fault is output.
Dependency:
Refer to: r2198
Description:
Sets the response when evaluating the load monitoring.
Values:
0:
Load monitoring disabled
1:
A07920 for torque/speed too low
2:
A07921 for torque/speed too high
3:
A07922 for torque/speed out of tolerance
4:
F07923 for torque/speed too low
5:
F07924 for torque/speed too high
6:
F07925 for torque/speed out of tolerance
Dependency:
Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, r2198
Refer to: A07920, A07921, A07922, F07923, F07924, F07925
Note:
The response to the faults F07923 ... F07925 can be set.
p2177[0...n]
Motor locked delay time / Mot lock t_del
SERVO, VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_LIM_REF
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8012
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
65.000 [s]
1.000 [s]
p2178[0...n]
Motor stalled delay time / Mot stall t_del
VECTOR
Can be changed:
U, T
Calculated:
CALC_MOD_REG
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
8012
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [s]
10.000 [s]
0.010 [s]
p2181[0...n]
Load monitoring response / Load monit resp
SERVO (Extended
msg), VECTOR
(Extended msg)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
DDS, p0180
Func. diagram:
8013
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0 6
0