![Siemens SINAMICS S Series List Manual Download Page 1436](http://html.mh-extra.com/html/siemens/sinamics-s-series/sinamics-s-series_list-manual_12654271436.webp)
Faults and Alarms
List of faults and alarms
3-1436
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A01007
POWER ON for DRIVE-CLiQ component required
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ component must be powered-up again (POWER ON) as, for example, the firmware was updated.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Note:
For a component number = 1, a POWER ON of the Control Unit is required.
Remedy:
Switch-out the power supply of the specified DRIVE-CLiQ component and switch-in again.
F01008 (N)
Upload not possible
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
It is neither possible to upload parameters nor the topology because this would lead to inconsistent data sets due to
the activation of certain drive functions.
Fault value (r0949, interpret decimal):
Number of active functions that result in the upload being canceled.
Remedy:
For all vector drives, check the following functions and if required, de-activate:
- rotating measurement (p1960).
- record the friction characteristic (p3845).
- synchronize line-drive (p3800).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A01009 (N)
CU: Control board overtemperature
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r0037[0]) of the control board (Control Unit) has exceeded the specified limit value.
Remedy:
- check the air intake for the Control Unit.
- check the fan for the Control Unit (only for CU310).
Note:
The alarm automatically disappears after the limit value has been fallen below.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F01010
Drive type unknown
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An unknown drive type was found.
Fault value (r0949, interpret decimal):
Drive object type (refer to p0101, p0107).
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade the firmware release.
- contact the Hotline.