Parameters
List of parameters
1-810
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the normalization characteristic for the analog outputs of Terminal Board 30 (TB30).
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Note:
The parameters for the characteristic do not limit.
Description:
Sets the normalization characteristic for the analog outputs of terminal module 31 (TM31).
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
Refer to: r4076, p4076
Notice:
This parameter is automatically overwritten when the analog output type is changed (p4076).
Note:
This parameter is overwritten if p4076 (type of analog output) is changed.
The parameters for the characteristic do not limit.
Description:
Sets the normalization characteristic for the analog outputs of Terminal Board 30 (TB30).
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V) of the 2nd value pair of the characteristic.
Index:
[0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Note:
The parameters for the characteristic do not limit.
p4079[0...1]
TB30 analog outputs, characteristic value x2 / TB30 AO char x2
TB30
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9106
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
100.00 [%]
p4079[0...1]
TM31 analog outputs, characteristic value x2 / TM31 AO char x2
TM31
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9572
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
100.00 [%]
p4080[0...1]
TB30 analog outputs, characteristic value y2 / TB30 AO char y2
TB30
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
9106
P-Group:
Terminals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
-11.000 [V]
11.000 [V]
10.000 [V]