Parameters
List of parameters
1-706
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays the status of the line supply PLL.
Values:
0:
Initialization running
1:
Error when synchronizing
2:
Line analysis
3:
Calculation line data
4:
Pulse enable missing
5:
PLL calculation
6:
Final status controlled / smart mode
7:
Reserved
Description:
Sets the smoothing time for the line supply PLL.
Index:
[0] = Sensorless operation line supply frequency smoothing time
[1] = VSM operation line supply frequency smoothing time
Note:
It may be necessary to reduce the smoothing time for weak line supplies with high frequency fluctuations. There is
otherwise a risk of brief orientation errors and the infeed could fail.
Description:
Displays the PLL system deviation.
Description:
Displays the PLL system deviation after filtering.
Dependency:
Refer to: p3458
r3452
Infeed PLL status / INF PLL status
A_INF, S_INF
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0000 bin
0111 bin
-
p3458[0...1]
Infeed PLL smoothing time / INF PLL t_smooth
A_INF, S_INF
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1.0 [ms]
1000.0 [ms]
[0] 23.1 [ms]
[1] 9.1 [ms]
r3460
Infeed PLL system deviation / INF PLL ctrl_dev
A_INF, S_INF
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [°]
- [°]
- [°]
r3461
Infeed PLL system deviation after filtering / INF PLL ctrl_devSm
A_INF, S_INF
Can be changed:
-
Calculated:
-
Access level:
4
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
-
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- [°]
- [°]
- [°]