Parameters
List of parameters
1-696
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Displays the status of NAMUR signal bit bar.
The faults or alarms are assigned to the appropriate signaling/message classes and influence a specific message
bit.
Description:
Displays the global status word for messages.
The appropriate bit is set if at least one message is present at the drive objects.
Note:
The status bits are displayed with delay.
Description:
Sets the threshold value for the "excitation current outside tolerance" message for the excitation current monitoring.
If the absolute value of the difference between the excitation current setpoint and actual value (r1641 - r1626)
exceeds the threshold value and the hysteresis is longer than the selected delay time, then fault F07913 is output.
This fault is withdrawn when the threshold voltage is fallen below.
r3113.0...15
CO/BO: NAMUR message bit bar / NAMUR bit bar
All objects
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fault drive converter data electronics / soft-
ware error
Yes
No
-
01
Line supply fault
Yes
No
-
02
DC link overvoltage
Yes
No
-
03
Fault drive converter power electronics
Yes
No
-
04
Drive converter overtemperature
Yes
No
-
05
Ground fault
Yes
No
-
06
Motor overload
Yes
No
-
07
Bus error
Yes
No
-
08
External safety-relevant shutdown
Yes
No
-
09
Mot encoder fault
Yes
No
-
10
Error internal communications
Yes
No
-
11
Infeed fault
Yes
No
-
15
Other faults
Yes
No
-
r3114.9...11
CO/BO: Messages status word global / Msg ZSW global
CU_CX32, CU_S
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
09
Alarm present
Yes
No
8065
10
Fault present
Yes
No
8060
11
Safety message present
Yes
No
-
p3201[0...n]
Excitation current outside the tolerance threshold value / I_exc n.Tol thresh
VECTOR
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
-
P-Group:
Messages
Units group:
-
Unit selection:
-
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.1 [%]
100.0 [%]
10.0 [%]