Faults and Alarms
List of faults and alarms
3-1744
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A40103
Alarm at DRIVE-CLiQ socket X103
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X103.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
A40104
Alarm at DRIVE-CLiQ socket X104
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X104.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
A40105
Alarm at DRIVE-CLiQ socket X105
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X105.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
F40799
CU-Link: Configured transfer end time exceeded
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The configured transfer end time when transferring the cyclic actual values was exceeded.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- contact the Hotline.
F40801
CX32 DRIVE-CLiQ: Sign-of-life missing
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the Control Unit and the controller extension involved.
The nodes do not send and receive in synchronism.
Fault value (r0949, interpret hexadecimal):
0A: The sign-of-life bit in the receive telegram is not set.
Remedy:
- carry out a POWER ON.
- replace the component involved.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
F40820
CX32 DRIVE-CLiQ: Telegram error
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the Control Unit and the controller extension involved.
Fault value (r0949, interpret hexadecimal):
01: CRC error.
02: Telegram is shorter than specified in the length byte or in the receive list.
03: Telegram is longer than specified in the length byte or in the receive list.