List of parameters
Parameters
1-157
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note:
The parameter influences the temperature adaptation of the stator resistance.
The motor identification sets the cable resistance to 20% of the measured total resistance if p0352 is zero at the
time that the measurement is made. If p0352 is not zero, then the value is subtracted from the measured total stator
resistance to calculate stator resistance p0350. In this case, p0350 is a minimum of 10% of the measured value.
Exception:
For parallel circuit configurations with one winding system (p07003 = 0), the cable resistance is directly measured.
It is important to note that only the component of an individual Motion Module is entered into p0352.
Description:
Sets the series inductance.
Note:
For the automatic calculation with p0340 = 1 or 3, the calculation of p0348 is influenced by p0353 if p0348 was 0.
For the automatic calculation with p0340 = 1, 3 or 4, the calculation of p1715 is influenced by p0353.
Description:
Sets the rotor/secondary section resistance of the motor at the ambient temperature p0625.
For separately-excited synchronous motors: Sets the damping resistance in the rotor direction (d-axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910) (not for separately-excited synchronous motors).
Dependency:
Refer to: p0625
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Sets the damping resistance of the separately-excited synchronous motor quadrature to the rotor direction (q axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2).
p0353[0...n]
Motor series inductance / Mot L_series
SERVO, VECTOR
Can be changed:
C2(3), U, T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
15_1
Unit selection:
p0349
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.000 [mH]
1000000.000 [mH]
0.000 [mH]
p0354[0...n]
Motor rotor resistance cold / damping resistance d axis / Mot R_r cold / RDd
SERVO, VECTOR
Can be changed:
C2(3), U, T
Calculated:
CALC_MOD_EQU
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
16_1
Unit selection:
p0349
Not for motor type:
PEM, REL
Expert list:
1
Min Max
Factory
setting
0.00000 [Ohm]
300.00000 [Ohm]
0.00000 [Ohm]
p0355[0...n]
Motor damping resistance, q axis / Mot R_damp q
VECTOR
Can be changed:
C2(3), U, T
Calculated:
CALC_MOD_EQU
Access level:
3
Data type:
Floating Point
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
16_1
Unit selection:
p0349
Not for motor type:
ASM, PEM, REL
Expert list:
1
Min Max
Factory
setting
0.00000 [Ohm]
300.00000 [Ohm]
0.00000 [Ohm]