Parameters
List of parameters
1-126
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the alarm threshold for a line undervoltage condition.
The setting is made as a percentage of the drive unit supply voltage (p0210).
Dependency:
Refer to: p0222, p0224, p0225, p0226, p3421, p3422
Refer to: A06105
Note:
If synchronizing voltages are not detected, the line supply voltage is estimated using a model. It is therefore impor-
tant to ensure that drive unit data is correctly specified.
Description:
Sets the trip threshold for the line supply undervoltage.
The setting is made as a percentage of the drive unit supply voltage (p0210).
Dependency:
Refer to: p0282
Refer to: F06100
Notice:
For Active Line Modules booksize, the following applies:
When operated without Active Interface Module (p0220 = 41 ... 45), the minimum shutdown threshold is 75 %.
Description:
Sets the alarm threshold for an excessively high line frequency.
Dependency:
Set as a percentage of the rated line frequency.
Refer to: p0211
Description:
Sets the alarm threshold for an excessively low line frequency.
Dependency:
Set as a percentage of the rated line frequency.
Refer to: p0211
p0282
Line supply undervoltage, alarm threshold / V_l_under A thresh
A_INF, S_INF
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8860, 8960
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
10 [%]
100 [%]
85 [%]
p0283
Line supply undervoltage, shutdown (trip) threshold / V_l_under tr_thrsh
A_INF, S_INF
Can be changed:
C2(1), T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8860, 8960
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
10 [%]
100 [%]
75 [%]
p0284
Line supply frequency exceeded, alarm threshold / f_l_exc A thresh
A_INF, S_INF
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8864, 8964
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
100.0 [%]
300.0 [%]
110.0 [%]
p0285
Line supply frequency fallen below, alarm threshold / f_l_under A thresh
A_INF, S_INF
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Floating Point
Dynamic index:
-
Func. diagram:
8864, 8964
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
0.0 [%]
100.0 [%]
90.0 [%]