Faults and Alarms
List of faults and alarms
3-1734
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F35886
CU DRIVE-CLiQ: Error when sending DRIVE-CLiQ data
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the Control Unit and the Terminal Module (TM)
involved. Data were not able to be sent.
Fault value (r0949, interpret hexadecimal):
41: Telegram type does not match send list.
Remedy:
Carry out a POWER ON.
F35887
CU DRIVE-CLiQ: Component fault
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
Fault detected on the DRIVE-CLiQ component (Terminal Module) involved. Faulty hardware cannot be excluded.
Fault value (r0949, interpret hexadecimal):
20: Error in the telegram header.
23: Receive error: The telegram buffer memory contains an error.
42: Send error: The telegram buffer memory contains an error.
43: Send error: The telegram buffer memory contains an error.
60: Response received too late during runtime measurement.
61: Time taken to exchange characteristic data too long.
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
F35895
CU DRIVE-CLiQ: Cyclic data transfer error
Drive object:
All objects
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the Control Unit and the Terminal Module (TM)
involved.
Fault value (r0949, interpret hexadecimal):
0B: Synchronization error during alternating cyclic data transfer.
Remedy:
Carry out a POWER ON.
See also: p9915 (DRIVE-CLiQ data transfer error shutdown threshold master)
F35896
CU DRIVE-CLiQ: Inconsistent component characteristics
Drive object:
All objects
Reaction:
A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
VECTOR: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The properties of the DRIVE-CLiQ component (Terminal Module), specified by the fault value, have changed in an
incompatible fashion with respect to the properties when booted. One cause can be, e.g. that a DRIVE-CLiQ cable
or DRIVE-CLiQ component has been replaced.
Fault value (r0949, interpret decimal):
Component number.
Remedy:
- when replacing cables, only use cables with the same length as the original cables.
- when replacing components, use the same components and firmware releases.
- carry out a POWER ON.