List of parameters
Parameters
1-759
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description:
Sets the warm-up time.
For an automatic trace (record) to start, the highest selected speed (p3829) is approached and this time is held.
After this, the measurement is started with the highest speed.
Dependency:
Refer to: p3829, p3845
Description:
Sets the number of Braking Modules connected in parallel in a DC link.
Note:
The parameter can only be written to if the infeed is in the commissioning mode (p0010 = 2).
Description:
Signal to energize terminal X21.1 "inhibit/acknowledgement" on the Braking Module.
This binector output is used as signal source to interconnect to a digital output.
For "booksize" formats the digital output must be connected to terminal X21.1 and for "chassis" formats the digital
output must be connected to terminal X21.5 of the particular Braking Module.
Warning:
It must be carefully ensured that the binector outputs BO: p3861.n are correctly connected and also that the appro-
priate digital outputs are correctly connected-up.
If the interconnections/connections are incorrect and if the Braking Module develops a fault condition, then the soft-
ware could execute a different (incorrect) function via the binector outputs BO: p3861.n.
p3847[0...n]
Friction characteristic record warm-up time / Frict rec t_warm
SERVO, VECTOR
(n/M)
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Floating Point
Dynamic index:
DDS, p0180
Func. diagram:
7010
P-Group:
Functions
Units group:
-
Unit selection:
-
Not for motor type:
REL
Expert list:
1
Min Max
Factory
setting
0.000 [s]
3600.000 [s]
0.000 [s]
p3860
Number of Braking Modules connected in parallel / BM qty par_cct
A_INF (Brk Mod ext),
B_INF (Brk Mod ext),
S_INF (Brk Mod ext)
Can be changed:
C2(2)
Calculated:
-
Access level:
3
Data type:
Unsigned8
Dynamic index:
-
Func. diagram:
9951
P-Group:
Converter
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
1 8
1
r3861.0...7
BO: Braking Module inhibit/acknowledgement / BM inhib/ackn
A_INF (Brk Mod ext),
B_INF (Brk Mod ext),
S_INF (Brk Mod ext)
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
9951
P-Group:
Commands
Units group:
-
Unit selection:
-
Not for motor type:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Inhibit/acknowledge Braking Module 1
High
Low
-
01
Inhibit/acknowledge Braking Module 2
High
Low
-
02
Inhibit/acknowledge Braking Module 3
High
Low
-
03
Inhibit/acknowledge Braking Module 4
High
Low
-
04
Inhibit/acknowledge Braking Module 5
High
Low
-
05
Inhibit/acknowledge Braking Module 6
High
Low
-
06
Inhibit/acknowledge Braking Module 7
High
Low
-
07
Inhibit/acknowledge Braking Module 8
High
Low
-