Faults and Alarms
List of faults and alarms
3-1634
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F30809
Power unit: Switching information not valid
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
For 3P gating unit:
The last switching status word in the setpoint telegram is identified by the end ID. Such an end ID was not found.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade the firmware release.
- contact the Hotline.
A30810 (F)
Power unit: Watchdog timer
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
When booting it was detected that the cause of the previous reset was an SAC watchdog timer overflow.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade the firmware release.
- contact the Hotline.
Reaction upon F:
NONE (OFF2)
Acknowl. upon F:
IMMEDIATELY
F30820
Power unit DRIVE-CLiQ: Telegram error
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the Control Unit and the power unit involved.
Fault value (r0949, interpret hexadecimal):
01: CRC error.
02: Telegram is shorter than specified in the length byte or in the receive list.
03: Telegram is longer than specified in the length byte or in the receive list.
04: The length of the receive telegram does not match the receive list.
05: The type of the receive telegram does not match the receive list.
06: The address of the component in the telegram and in the receive list do not match.
07: A SYNC telegram is expected - but the received telegram is not a SYNC telegram.
08: A SYNC telegram is not expected - but the received telegram is a SYNC telegram.
09: The error bit in the receive telegram is set.
10: The receive telegram is too early.
Remedy:
- carry out a POWER ON.
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
F30835
Power unit DRIVE-CLiQ: Cyclic data transfer error
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communications error has occurred between the Control Unit and the power unit involved. The nodes
do not send and receive in synchronism.
Fault value (r0949, interpret hexadecimal):
21: The cyclic telegram has not been received.
22: Timeout in the telegram receive list.
40: Timeout in the telegram send list.
Remedy:
- carry out a POWER ON.
- replace the component involved.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)